3 Operation by using the LCD menu
3-4 Operation by using the LCD menu
BL50T/BL75T/BL100T
44
3-4-3 Operation by using the LCD menu
☆
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu item
Description
Value
Menu type
Settings
Local Setting
Audible Alarm
Set the condition for the buzzer to sound. Buzzer setting:
ON (factory default),
OFF during backup operation, Always OFF
Standard
Calendar Setting
Set calendar information for the UPS.
Calendar settings: Year, month, day, hour,
minute
UPS Installation
Set the date when the use of the UPS
started.
UPS usage start date: Year, month, day
(Factory default: 2018/1/1)
UPS Life Count
Set the operation of the UPS life counter.
UPS life counter:
Enabled (factory default), Disabled
Menu Type
Select the menu to be displayed. When
"Standard" is selected, only the frequently
used items are displayed.
Menu type:
Standard (factory default),
Advanced
In/Out Settings
AC I/P Sensitivity
Set the input voltage sensitivity. (Note 1)
Input voltage sensitivity:
Standard (factory default), High sensitivity,
Low sensitivity
Standard
Frequency Range
☆
Switch the frequency range mode.
Frequency range:
Normal range (factory default),
Wide range
Advanced
Transfer Sensitivity
☆
Set the sensitivity by which the operation is
switched to backup operation.
Transfer sensitivity:
Standard (factory default), High sensitivity
Boot Settings
Auto Reboot
Set automatic reboot from a power outage. Automatic reboot:
Enabled (factory default), Disabled
Standard
Cold Start
Set whether to enable the "Cold Start"
function, which can start up the UPS
without "AC input".
Cold start:
Disabled (factory default), Enabled
Reboot Delay Time
Set the delay time for recovery from a
power outage.
Reboot delay time:
0 to 999 seconds
(Factory default: 15 seconds)
Advanced
Reboot Batt.level
Set the battery level for reboot.
Reboot battery level:
0 to 100% (Factory default: 0%)
Auto Reboot Mode
Set the mode for reboot.
Auto boot mode:
Mode A (factory default), mode B
Power SW OFF Mode
Switch the operation mode for the Power
switch.
Power switch off mode:
UPS shutdown (factory default),
UPS + PC shutdown
Battery Settings
Function Test
Set the interval of self-diagnostic test
execution.
Function test:
At startup/every four weeks (factory
default),
At startup, Every four weeks, Disabled
Standard
Batt.life Counter
Sets whether to notify the user about the
battery's end of life. (Note 2)
Battery life counter:
Enabled (factory default), Disabled
Battery Installation
Set the date when the battery was
replaced.
Battery installation date:
Year, month, and day
(Factory default: 2018/1/1)
Max.backupTime
☆
Set the output of the UPS to stop after a
specified period of time.
Maximum backup time:
Disabled (factory default)
Enabled: 10 to 999 seconds
Enabled: 1 to 9999 minutes
Advanced