.Installation and connection
21
When you finish connecting the unit, confirm that the backup operation works properly.
Check that the Battery Mode is performed normally according to the following procedure.
(In this operation check, the effects of a power failure are reproduced by disconnecting the AC input
plug from the wall outlet (commercial power).)
(1) Press and hold the unit’s power switch for 2 seconds or longer to turn ON the power.
The beeper sounds and the current settings are displayed on the LCD.
Self-diagnosis starts automatically.
When the self-diagnosis test finishes normally, the unit’s operation switches to commercial power
and the status indication below is displayed.
(When the battery voltage is low, the self-diagnostic test is not performed and output begins imme-
diately via commercial power.)
(2) Bring all the connected devices into operation.
(Including devices connected to the AC outlet of your PC.)
Operate the connected devices in a way that allows the power supply to be stopped at any time.
The unit was charged before shipment, but it may have self-discharged during shipment, resulting
in a reduced backup time. We recommend charging the unit before use.
(3) Under this condition, check the the unit's LCD and beep sound.
Are they in the same status as shown below?
Status indicator
Beep
None
Power supply output receptacles
Outputs power (connected devices are powered)
If the same as the one shown above: → The operation is normal. Proceed to (4).
If not the same as the one shown above: → The operation is abnormal. One of the cases described in
"4. Display and beeps when there is an equipment failure"
of "3-3 Interpreting a beep and displays" on page 28 must
apply.
Take necessary measures and then proceed to (4).
(4) Disconnect the unit’s AC input plug from the wall outlet (commercial power).
The unit enters Battery Mode.
2-5 Checking the operation
Status indicator
Description
Power switch “ON”
Operating normally
ON
OFF
ON, OFF, or blinking
depending on status
Summary of Contents for BN150R
Page 69: ...57 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Page 70: ...BN75R BN150R BN300R 10 58 2 FA OA 2...
Page 71: ...10 Troubleshooting 59 AC 50 60Hz AC AC AC AC 3P 2P AC AC...
Page 72: ...BN75R BN150R BN300R 10 60 5cm UPS UPS AC AC AC200V 240V AC200 240V...
Page 73: ...10 Troubleshooting 61 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 4 5 30 1mA...
Page 74: ...BN75R BN150R BN300R 10 62 AC UPS AC UPS...
Page 75: ...10 Troubleshooting 63 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Page 76: ...BN75R BN150R BN300R 10 64 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Page 80: ...BN75R BN150R BN300R 68 BN300R 438 87 OMRON BN300R ESC 650...