3
.Operation
29
No.
Icon
Mode
Beep
Discription
Solution
8
Battery
mode
Intermittent
4-second
Backup is operating due to power
failure or AC input error
Shut down the connected
devices to stop them.
Battery low
Intermittent
1-second
Battery level is low, so output will
stop soon.
9
Battery
empty
None
Battery is dead, so output
stopped
Charge the battery.
Battery not
connected
Intermittent
2-second
Battery is not connected
Connect the battery.
10
Battery
weak
Intermittent
2-second
intervals
The self-diagnostic test
determined that the battery was
deteriorated, or the battery life
counter went off-scale
Replace the battery
You can replace the weak battery
with a separately purchased
replacement battery as needed
11
Over load
Intermittent
0.5-second
intervals
There are too many connected
devices and the rated capacity is
exceeded
Reduce the number of connected
devices until the display appears
as in status No.2
12
UPS error
Continuous There is the internal error
Check the displayed message
●
Load/battery level meter
The load level meter displays the power consumption of the connected devices as a percentage.
The maximum connection capacity is displayed as 100%. (The maximum connection capacity var-
ies depending on the AC input plug setting.)
See also
“2-4 Connecting the AC input” → Page 17
[Example]
•
BN75R: Displays 750VA/680W as 100%
•
BN150R: Displays 1500VA/1350W as 100%
(when the AC input plug setting is "20A" and the voltage sensitivity setting is "Standard")
•
BN300R: Displays 3000VA/2700W as 100%
(when the AC input plug setting is "Hard wire")
The battery level meter displays the remaining battery level as a percentage.
Summary of Contents for BN150R
Page 69: ...57 Notes of Chinese 10 UPS UPS 1 FA OA Windows UPS...
Page 70: ...BN75R BN150R BN300R 10 58 2 FA OA 2...
Page 71: ...10 Troubleshooting 59 AC 50 60Hz AC AC AC AC 3P 2P AC AC...
Page 72: ...BN75R BN150R BN300R 10 60 5cm UPS UPS AC AC AC200V 240V AC200 240V...
Page 73: ...10 Troubleshooting 61 AC AC AC AC AC ON OFF AC INPUT PROTECTION 25 4 5 30 1mA...
Page 74: ...BN75R BN150R BN300R 10 62 AC UPS AC UPS...
Page 75: ...10 Troubleshooting 63 AC AC 50 60Hz 25 25 6 40 2 AC AC...
Page 76: ...BN75R BN150R BN300R 10 64 DC250V UPS 200V http www fa omron com cn Pb AC AC 50 60Hz...
Page 80: ...BN75R BN150R BN300R 68 BN300R 438 87 OMRON BN300R ESC 650...