35
4
BU
1002
SWG / BU
3002
SWG
●
Setting for whether or not to perform battery test (setting switch
3
)
… Factory setting: OFF
1 2
5
3 4
8
6 7
ON
DIP
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
●
Auto startup mode setting (setting switch
4
) … Factory setting: OFF
OFF: (Mode A) After UPS stopped, the UPS is automatically started immediately when “ON” is
detected for the AC input.
ON: (Mode B)
After UPS stopped, the UPS is automatically started in the AC input’s “OFF to ON”
timing that is detected.
(Definition of AC input OFF: When AC input is OFF for 1 second or more)
* Setting switch
4
is valid when the auto startup after recovery from power failure setting (setting switch
2
) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup stop
signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the
unit operates in Mode A regardless of this setting.
1 2
5
3 4
8
6 7
ON
DIP