2 Installation and connection
2-2 How to connect devices to back up
BU150R
30
■
Group-based control of "power supply output"
When the attached automatic shutdown software is used, you can use the power supply
output group-based control function.
The power supply output receptacles of the UPS are divided into three groups, Groups A, B,
and C.
•
Each of "power supply output" Groups B and C can delay its output start time or hasten
its output stop time independently of "power supply output" Group A.
•
The output start and stop time control function can be controlled by the automatic
shutdown software "PowerAct Pro" or "SNMP/Web card".
•
While the UPS is running, ON/OFF control can be performed on power supply output
from the automatic shutdown software.
•
The above delay setting and ON/OFF control can be performed on each of "power
supply output" Groups B and C independently.
The order in which such equipment as servers and peripherals starts up can be set by
using this function.
In addition, forcible ON/OFF control on an output receptacle can be remotely performed.
■
Fixing power cables
A connected power cable can be fixed with a retaining clip (BUX150R) provided as an
option.
This clip prevents an input plug from being detached in such a case as when the cable is
pulled.
Power supply output
group A
Power supply output
group C
Power supply output
group B
Output ON
Output OFF
Time setting
Time setting
Time setting
Time setting
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...