3 Check and start operation
3-1 The name and function for the operation and display
BU150R
38
●
BSsignal range setting ("Setting" switch 5)
Factory setting: OFF
OFF: BS signal always effective (can be received)
The "power supply output" of the UPS can be stopped by turning the backup power
supply stop signal (BS) "ON" for ten seconds or longer.
ON: BS signal effective (can be received) for backup operation only (cannot be received
during commercial operation)
The "power supply output" of the UPS can be stopped by turning the backup power
supply stop signal (BS) "ON" for 0.01 seconds (10 milliseconds) or longer.
When you do not want to stop the UPS even if the backup power supply stop signal
(BS) comes in during commercial operation, make this setting.
●
Logic of Remote on/off signal ("Setting" switch 6)
Factory setting: OFF
OFF: UPS start shutdown process when detecting close condition of remote input signal.
ON: UPS start shutdown process when detecting open condition of remote input signal.
●
AC input plug selection ("Setting" switch 8)
Factory setting: OFF
OFF: Use 15Aplug
ON
:
Use 20A plug