3 Check and start operation
3-1 The name and function for the operation and display
BU150R
35
3
3-1-4 Setting Switch
After changing the "Setting" switch, follow the procedure described below.
After changing the "Setting" switch, turn off the AC input and pull off the AC input plug ,
wait until the status indicator is completely OFF, and then turn on the AC input.
Use a fine-pointed tool such as a small screwdriver to maneuver the switch's lever.
●
Setting switch function list
Bit
Function to set
OFF side
ON side
1
Beeper sound in the
event of power
failure, etc.
Beeper
sounds
Beeper
does not
sound
2
Auto startup after
recovery from
power failure
Auto startup
is performed
Auto startup
is not
performed
3
ON/OFF the test
once every 4 weeks
Test is
performed
Test is not
performed
4
Auto startup mode
by BS signal
Mode A
Mode B
5
BS signal range
Always
enabled
Enabled for
backup
operation
only
6
Logic of Remote
on/off signal
Normally
opened
Normally
closed
7
-
-
-
8
Select AC input plug 15Aplug
20APlug
●
Setting for beeper sound in the event of power failure, etc. ("Setting"
switch 1)
Factory setting: OFF
OFF
:
The beeper sounds when an alarm is necessary.
ON
:
The beeper does not sound for backup operation or battery replacement. The beeper
sounds for other errors (connection capacity exceeded, operation error, etc.).
1
2
3
4
5
6
7
8
ON
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...