3 Check and start operation
3-4 Interpreting beeps and displays
BU150R
52
(
2
)
When "Power" switch is "OFF"
No.
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replacement
lamp
Beep
Charging
Description
Solution
35
Continuous
OFF
Stopped charging due to abnormal
rise in battery charge voltage.
There is a problem
with the UPS.
Contact our sales
representative or
Omron Electronic
Systems &
Equipment
Customer Support
Center.
36
Continuous
OFF
Stopped charging due to abnormal
drop in battery charge voltage.
(Same as
above.)
Continuous
OFF
External Fan Error.
(Same as
above.)
3-4-5 Display and beep for battery replacement
No
Status
indicator
Power
supply
output
lamp
Battery
mode
lamp
Battery
replacement
lamp
Beep
Charging
Description
Solution
37
Intermittent
2-second
intervals
ON
The
self-diagnosis
test detected a
weak battery
(warning only,
output
continues).
Replace the battery.
You can replace the
weak battery with a
separately
purchased
replacement battery
as needed.See also
"4-2 Replacing the
battery"( P.65 )
38
Intermittent
2-second
intervals
ON
Battery life
counter went
off-scale.
(Warning only.
Outputs
continue.)
(Same as above.)
39
――
――
――
None
――
Battery life
counter has
been reset.
Be sure to reset the
battery life counter
after replacing the
battery.
See also
Summary of Contents for BU150R
Page 22: ...2 Installation and connection 2 1 Installation BU150R 22 Incorrect Positions...
Page 92: ...7 How to use option cards 7 3 SNMP Web card BU150R 92 7 3 SNMP Web card LAN 10 100...
Page 102: ...10 References 10 2 Dimensions BU150R 102 Stand for vertical layput 200 200 70 50 70 50...
Page 103: ...10 References 10 2 Dimensions BU150R 103 10 Rubber feet 23 25 405 50 40 358 40 3...
Page 104: ...10 References 10 2 Dimensions BU150R 104 Using Ear brackets 44 5 22 0 13 5 455 25 465...