7 How to use option cards
7-2 Contact I/O card
BU150R
91
7
7-2-2 Specifications
Output signals (
BU
、
BU
、
BL
、
BL
、
TR
、
TR
、
WB
、
WB)
Relay ratings
Applicable voltage : DC30V or less
Maximum current :
2A (for resistive load)
1A (for inductive load)
UPS Stop Signal input (
BS
、
BS)
Input voltage : High (ON)
DC8V - 24V (for the 24V setting)
DC5V - 12V
(
for the 12V setting
)
LOW (OFF)
DC0.7V or less
Remote ON/OFF
Voltage between terminals: DC5V
Current when closed:
max. 10mA
* For details, see the manual attached to a contact I/O card.