2-2-2 BUM300R connection procedure / Connectable UPS : BU200RW/BU300RW
(1) Connect the additional battery cable to the UPS and the connector on the back of the battery unit.
Connect the signal connection cable to the additional battery signal connector also.
(2) Turn ON the overcurrent protection switch on the back of the battery unit and the INPUT PROTECTION
switch (input overcurrent protection switch) on the back of the UPS.
When a 2400W device is connected, the backup time is approximately 18 minutes (initial battery
value at an ambient temperature of 20
°
C).
When the battery is completely discharged, it takes 24 hours to charge.