28
<After replacing the battery during operation...>
Press the beep stop/test button for 5 to 10 seconds, to perform a self-diagnostic test. Normal
operation resumes after the test for about 10 seconds. If the beeping sounds, the beeping stops at
the
fi
rst press of the button and starts test in the second press of the button.
If the battery replacement indicator is ON and beep sounds before replacing the battery, the
indicator is OFF and beep stops after test completion, and normal operation resumes.
<After replacing the battery with operation stopped...>
Connect the AC input to a commercial power source, and turn ON the overcurrent protection switch
and UPS power switch. When operation starts, the self-diagnostic test is automatically performed.
Normal operation resumes after the 10-second test.
Write the date you start using the battery on the included battery replacement date label.
Also, the UPS monitoring software included with the UPS enables to, keep a record of the
software usage start date.
Pb
Notes
This unit uses a lead acid battery.
●
Lead acid batteries are a valuable recyclable resource. Please recycle.
●
For information about recycling, please contact our Electronic Systems & Equipments
repair center.