5 Measuring the backup time
5-2 Estimated backup time
BW40T/BW55T/BW100T/BW120T
34
2.
Add the values converted into W to obtain the total capacity of the connected
devices.
Estimated backup time
Backup time-table
* These backup times are for reference only. Times may vary according to battery
life and external environmental conditions (temperature, etc.).
* The maximum value of the estimated backup time display is 99.9 minutes on
LCD.
Load/Type
20 40 50 60 80 100 120 150 180 200 210 240 250 270 300 330 340 400 500 600 610 700 720 730
BW40T
105 60 50 36 28 22 18 13 10 8
7
6 5.4 -
-
-
-
-
-
-
-
-
-
-
BW55T
105 60 50 36 28 22 18 13 10 8
7
6 5.4 5 4.5 4 3.6 -
-
-
-
-
-
-
BW100T
220 120 100 84 64 50 40 32 24 20 19 17 16.5 15 13 11.5 11 8
5 4.5 4.3 -
-
-
BW120T
220 120 100 84 64 50 40 32 24 20 19 17 16.5 15 13 11.5 11 8
5 4.5 4.3 4.2 4 3.6