System Settings and Auto Wait Time Setting
Section 5-3
5-3
System Settings and Auto Wait Time Setting
Parameter settings (including System Settings and an Auto Wait Time Set-
ting) can be adjusted to the user application to optimize the performance and
reliability of the ID Sensor Unit. Although the default settings can be used for
most applications without any problems, the parameters can be changed to
optimize the system.
5-3-1
System Settings
Communications Test
Mode Switch Setting
The communications test mode switch on the Unit’s front panel can be used
to enable and disable the communications test. The communications test
mode switch can be set to disable test mode to prevent accidentally entering
test mode.
Verification Setting
Verification can be enabled for write operations, or verification can be dis-
abled to shorten the communications time. The verification setting is valid for
all commands except for Read and Data Check with a processing specifica-
tion of verification.
DM Area address
Bit No.
Description
Default
Head 1 of
CS1W-
V600C11,
CS1W-
V600C12,
CJ1W-
V600C11,
or CJ1W-
V600C12
Head 2 of
CS1W-
V600C12
or CJ1W-
V600C12
m
m + 100
08 to
11
0
Communications test mode
switch enabled.
0
(Enabled)
1
Communications test mode
switch disabled. (Always Nor-
mal Mode.)
DM Area address
Bit No.
Description
Default
Head 1 of
CS1W-
V600C11,
CS1W-
V600C12,
CJ1W-
V600C11,
or CJ1W-
V600C12
Head 2 of
CS1W-
V600C12
or CJ1W-
V600C12
m
m + 100
04 to
07
0
Verify write operations.
0
(Verifica-
tion)
1
Do not verify write operations.
Summary of Contents for CJ - 12-2004
Page 2: ...SYSMAC CS CJ Series ID Sensor Units Operation Manual Revised December 2004...
Page 3: ...iv...
Page 11: ...xii...
Page 55: ...36 Connections and Wiring Section 3 4...
Page 69: ...50 I O Data Allocations Section 4 3...
Page 91: ...72 Data Check Section 5 7...
Page 141: ...122 Sample Programming Appendix B...
Page 147: ...128 Revision History...