Troubleshooting using the IO Controller indicators
Section 8-2
119
IO Controller Unit response
The Unit is not capable to communicate on the PROFINET network and
therefore control to the IO Devices will be lost. he Unit will stop processing.
Records the error in the error log.
CIO Area Flags allocated to the IO Controller Unit
IO Controller status 2 (word n+6) bit 03 will be ON
Correction
Check the ethernet network for possible causes of disturbance. This can be
EMC influences, broken or shorted Ethernet cable, faulty connectors,
defective Ethernet switches or IO Devices and grounding problems to name a
few. This will result in interrupted data streams or broken messages.
8-2-3-4 Memory access errors
Special Unit error
/i
Likely cause
The PROFINET IO controller encountered an internal error and can not
continue.
IO Controller Unit response
The Unit will stop processing. Records the error in the error log.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the IO Controller. Replace the IO-Controller if the error recurs.
Memory access error
/i
Likely cause
During startup the IO Controller encountered a problem reading the
PROFINET IO Configuration file. This could be because the Unit started for
the first time and does not contain a configuration file yet.
IO Controller Unit response
The Unit is started and is capable to receive a PROFINET Configuration. It will
not initiate PROFINET IO Communication. Records the error in the error log.
CIO Area Flags allocated to the IO Controller Unit
IO Controller status 1 (word n+5) bit 07 will be OFF.
Correction
Use CX-ConfiguratorFDT to download a valid PROFINET IO Configuration in
the IO Controller. Or restore the Configuration from a Compact Flash
memory card. Replace the IO-Controller if the error recurs.
7-segment
MS indicator
NS indicator
Error log (Hex)
--
ON (red)
OFF
0601
7-segment
MS indicator
NS indicator
Error log (Hex)
E9
Flashing (green)
Flashing (red)
0602
Summary of Contents for CJ1W-CRM21
Page 1: ...CJ1W PNT21 PROFINET IO Controller Unit OPERATION MANUAL Cat No W12E EN 02 ...
Page 2: ......
Page 7: ...vii ...
Page 16: ......
Page 26: ...Basic operating procedure Section 2 4 10 ...
Page 46: ...Installation of Configuration Software Section 3 5 30 ...
Page 76: ...Generic IO Device DTM Section 4 4 60 ...
Page 156: ...140 ...
Page 164: ...146 ...
Page 168: ...150 ...
Page 170: ...Section 152 ...