Connection Status Codes and Error Processing
Section 14-3
01
0109
Error code returned from target:
The connection size settings
are different in the originator
and target.
Check the connection sizes set in the originator and target.
01
0110
Error code returned from target:
The target was unable to open
the connection, because of its
operating status, such as down-
loading settings.
Check whether
the tag data link is
stopped at the tar-
get. (Restart the
tag data link com-
munications with
the control bit.)
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Check whether the
tag data link is
stopped at the origi-
nator. (Restart the
tag data link commu-
nications with the
control bit.)
01
0111
Error code returned from target:
The RPI was set to a value that
exceeds the specifications.
This error does
not occur.
Check the target’s
RPI setting specifica-
tions.
Set the originator’s
RPI setting to 10
seconds or less.
01
0113
Error code generated by origi-
nator or returned from target:
Attempted to open more con-
nections than allowed by the
specifications (CJ2M: 32, other
CPU Units: 256).
Check the con-
nection settings
(number of con-
nections) at the
originator and tar-
get.
Check the connec-
tion settings (number
of connections) at
the originator and
target.
Check the connec-
tion specifications for
another company’s
devices.
Check the connec-
tion settings (number
of connections) at
the originator and
target.
Check the connec-
tion specifications for
another company’s
devices.
01
0114
Error code returned from target:
The Vendor ID and Product
Code did not match when open-
ing connection.
This error does
not occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Check the origina-
tor’s connection set-
tings.
01
0115
Error code returned from target:
The Product Type did not match
when opening connection.
This error does
not occur.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Check the origina-
tor’s connection set-
tings.
01
0116
Error code returned from target:
The Major/Minor Revisions did
not match when opening con-
nection.
Check the major
and minor revi-
sions set for the
target device and
connection. If nec-
essary, obtain the
EDS file and set it
again.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Confirm that the tar-
get device’s EDS file
is correct.
Check the origina-
tor’s connection set-
tings.
01
0117
Error code returned from target:
The tag set specified in the con-
nection’s target variables does
not exist.
Check whether
the originator and
target tag sets
and tags are set
correctly.
CJ2 CPU Units
Only: Check sym-
bol settings in the
CPU Unit.
Depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
Check the origina-
tor’s connection set-
tings. Check whether
the target’s tag sets
and tags are set cor-
rectly.
CJ2 CPU Units Only:
Check symbol set-
tings in the CPU
Unit.
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......