363
Connection Status Codes and Error Processing
Section 14-3
Unique OMRON Error Codes
01
0810
Error code returned from target:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
This error may
occur if the CPU
Unit’s cycle time
was long when
opening the con-
nection, the speci-
fied EM bank was
converted to file
memory, or some
problem in the
PLC caused the
PLC to stop.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data. If the PLC
has stopped,
identify and cor-
rect the error.
If the PLC system
is stopped, iden-
tify the cause of
the error from the
CPU Unit error
data.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the origi-
nator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer.)
01
0811
Error code generated in origina-
tor:
New data could not be obtained
from the CPU Unit when open-
ing connection. (The Unit will
automatically retry, and attempt
to open the connection again.)
This error may
occur if the CPU
Unit’s cycle time
was long when
opening the con-
nection, or the
specified EM bank
was converted to
file memory.
If the cycle time
was too long, the
problem will be
resolved automat-
ically. If the EM
bank is set as file
memory, change
the storage loca-
tion for the tag
data.
The meaning of this
error code is defined
by each vendor, so it
depends on the tar-
get’s specifications.
(Contact the target
device’s manufac-
turer.)
The meaning of this
error code is defined
by each vendor, so it
depends on the origi-
nator’s specifica-
tions.
(Contact the origina-
tor device’s manufac-
turer.)
Connection status
Source of error
Handling
General
Status
(hex)
Additional
Status
(hex)
Configuration 1
Configuration 2
Configuration 3
Summary of Contents for CJ2H-CPU6 - REV 02-2010
Page 2: ......
Page 4: ...iv...
Page 6: ...vi...
Page 14: ...xiv...
Page 18: ...xviii...
Page 38: ...12 Network Configurator Overview Section 1 5...
Page 58: ...32 Selecting the Network Devices Section 2 3...
Page 116: ...90 Auxiliary Area Data Section 4 5...
Page 222: ...196 Message Communications Errors Section 7 6...
Page 364: ...338 Using the Backup Tool Section 13 3...
Page 402: ...376 CS CJ series Ethernet Unit Function Comparison Appendix A...
Page 404: ...378 Ethernet Network Parameters Appendix B...
Page 406: ...380 TCP Status Transitions Appendix C...
Page 452: ...426 Precautions for Using Windows XP Vista or Windows 7 Appendix G...
Page 460: ...434 Index...
Page 462: ...436 Revision History...
Page 463: ......