5.10 Connecting 200-240 VAC Power
Table 5-10. User-Supplied 24 VDC Cable Description
Item
Description
1
eMB-40R Servo Controller
2
User-supplied Power Supply, 24 VDC
3
User-supplied shielded power cable
4
Frame Ground
5
Attach shield from user-supplied cable to ground screw on eMB-40R
Interface Panel
6
Attach shield from user-supplied cable to side of controller using star washer and
M3 x 6 screw.
7
Attach shield from user-supplied cables to frame ground on power supply.
NOTE:
We recommend that DC power be delivered over shielded cables, with
the shield connected to frame ground at the power supply, and to the ground
points shown. The length of wire from the cable shield to the grounds should be
less than 50 mm.
5.10 Connecting 200-240 VAC Power
WARNING:
ELECTROCUTION RISK
Ensure compliance with all local and national safety and electrical codes for
the installation and operation of the robot system.
WARNING:
ELECTROCUTION RISK
Appropriately-sized Branch Circuit Protection and Lockout / Tagout Capability
must be provided in accordance with the National Electrical Code and any
local codes.