6-4
Section
AR Area
86
Analog Outputs (CS1W-HCA22 Only)
Address
Bits
Function
Details
Controlled
by
Forced
set/reset
AR 14
00 to 15
Analog Output 1
Output Value
If END refresh is set as the analog output
method, the value set here by the user in
4-digit hexadecimal is output from analog
output 1 when analog output is refreshed.
If immediate refresh using instructions is set
as the analog output method, the value
output from analog output port 1 is stored
here in 4-digit hexadecimal for monitoring
when analog output is refreshed.
0 to 10 V, 0 to 5 V, 1 to 5 V:
FF38 to 1068 Hex
–10 to 10 V:
EA84 to 157C Hex
Note 1: The analog output method (END
refresh or immediate refresh using
instructions) is specified in bits 00 to 07 of
DM 6630 in the Unit Setup Area (00 Hex:
END refreshing). The setting applies to both
analog outputs 1 and 2.
Note 2: The output signal range is specified
in DM 6613.
Immediate
refresh
using
instructions:
Unit
END
refresh:
User
Enabled
AR 15
00 to 15
Analog Output 2
Output Value
Same as above (except that analog output 2
is used for analog output and the output
signal range is set in DM 6614).
AR 16
00
Analog Output 1
Conversion Enable
Bit
ON: D/A conversion enabled (an analog
signal is output)
OFF: D/A conversion is not performed
(analog output is held at the value specified
in DM 6613 nd DM 6614)
User
01
Analog Output 2
Conversion Enable
Bit
in DM 6613 and DM 6614)
Note: These bits are cleared when the
Customizable Counter Unit’s operating
mode is switched between RUN or
MONITOR mode and PROGRAM mode.
02 to 15
(Reserved by system.)
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......