9-3
Section
Troubleshooting Tables
131
Error
Unit indicators
Error
message
Error log
(SIOU code,
SR 23500
to
Error
flags
Meaning and corrective measures
RUN
OPN
ERC
ERH
me
age
(SIOU code,
details 1,
details 2)
to
SR 23507
flag
Power
interrupted
OFF
OFF
OFF
OFF
---
---
---
---
Power has been interrupted for at
least 10 ms.
Check power supply voltage and
power lines. Try to power-up again.
Unit WDT
error
OFF
OFF
OFF
OFF
---
---
---
---
A WDT timer error has occurred.
Change to PROGRAM mode and try
to power-up again.
Unit RAM
error
OFF
OFF
Lit
OFF
---
---
---
---
An error was detected when checking
RAM for shared memory with CPU
Unit at power-up.
Try to power-up again.
Memory
error
Lit
OFF
Lit
OFF
MEMORY
ERR
0360 Hex
00 Hex
F1 Hex
F1 Hex
SR 24906
The object program area overflowed
when the user program was
compiled.
Reduce the size of the program or try
Normal Execution Mode if
High-speed Execution Mode was
used initially.
SR 24907
Illegal instructions were found in the
program.
Make sure that all instructions in the
program are supported by the Unit
and retransfer the program.
SR 24908
Out-of-range operands were found in
the program.
Make sure that all addresses used in
the program are supported by the
Unit and retransfer the program.
SR 24909
A flash memory error occurred in the
Unit.
Change to PROGRAM mode, try to
power-up and transfer the program
again. For the CS1W-HCA22, check
AR 1712 to AR 1715 and perform the
following: If there is an error in the
user adjustments, clear the error and
readjust the settings. If the default
adjustments are being used, replace
the Unit.
SR 24910
A checksum error occurred in
read-only words in DM Area.
Reset the read-only words in DM
Area.
SR 24911
A checksum error occurred in Unit
Setup Area.
Reset the Unit Setup Area.
SR 24912
A checksum error occurred in the
user program or an instruction has
been used incorrectly.
Retransfer the program.
SR 24913
A checksum error has occurred in an
expansion instruction’s data.
Set all of the expansion instruction
settings again and retransfer the
program.
Lit
---
---
OFF
---
---
---
SR 24914
Memory contents could not be held
for a power interruption.
Download or reinput the required
data.
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......