Appendix A
Precautions when Using the CX-Programmer
144
Specifying Operand Addresses Not Supported by the CQM1H
The program cannot be transferred from the CX-Programmer to the Customizable Counter Unit if the following
operand values are set for STIM or ACC.
STIM: C2 = 001 or C3 = 001 to 003 when C1 = 011 or 012
ACC: M = 004 to 007
Either input the instructions from the Programming Console or use dummy operands and then correct them from
the Programming Console after transferring the program to the Customizable Counter Unit.
Note The program can be read from the Customizable Counter Unit to the CX-Programmer even if the above
operand values are set.
Setting the Unit Setup Area (DM 6600 to DM 6655)
To read or edit the Unit Setup Area, specify the DM Area addresses directly from the Memory Window. The
Memory Window can be accessed by selecting PLC – Edit – Memory from the Main Menu.
Reading the Error Log
To read the error log, specify the DM Area addresses (DM 6145 to DM 6199) directly from the Memory Window.
Checking the Ladder Program Size
The ladder program size, EM Area settings, and similar information cannot be checked from the CX-Programmer
because the “Device Type” is set to the CQM1H. To check the ladder program size, select View – Cross-Reference
Report and then subtract the unused UM size from the total UM size to determine the amount of UM that has been
used. The program cannot be transferred to the Customizable Counter Unit if the UM Area size is exceeded.
Monitoring the Cycle Time
The cycle time displayed when PLC – Edit – Cycle Time is selected will be 10 times the actual cycle time of the
Customizable Counter Unit. For example, if the CX-Programmer displays 10 ms, the cycle time is 1 ms.
Startup Operating Mode
If the User Setup Area is set to startup in the mode specified on the Programming Console (i.e., bits 00 to 07 of
allocated DM Area word m are set to 01 Hex) and the CX-Programmer is connected to the peripheral port on the
Customizable Counter Unit with an CS1W-CN226/626 or CS1W-CN118 + XW2Z-200/500S-CV Cable, the Custo-
mizable Counter Unit will start in RUN mode.
Change from Programming Console Cable to CX-Programmer Cable
If the cable connecting the Programming Console is removed and the cable connecting the CX-Programmer is
connected within 2 seconds, the CX-Programmer will not go online.
PLC Information Display
The PLC information display cannot be used. (The information for the CQM1H will be displayed.)
Symbol Names
Some of the CQM1H global symbols and memory area settings registered in advance on the CX-Programmer are
not correct for the Customizable Counter Unit. These are listed in the following tables.
•
The following symbols cannot be used when inputting instruction operands.
CQM1H symbol name
CQM1H memory contents
Customizable Counter
Unit area function
Function
CQM1H address
Unit area function
corresponding to CQM1H
address
P_Sec_Min
Upper bytes: Minutes
Lower bytes: Seconds
AR 18
Special I/O area (pulse
outputs or analog outputs)
P_Hour_Date
Upper bytes: Day of month
Lower bytes: Hours
AR 19
Special I/O area (pulse
outputs or analog outputs)
P_Low_Battery
Battery Low Flag
SR 25308
Reserved by system.
P_Month_Year
Upper bytes: Year
Lower bytes: Month
AR 20
Special I/O area (pulse
outputs or analog outputs)
P_Output_off_bit
Load OFF Bit
SR 25215
Reserved by system.
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......