3-5
Section
Fail-safe Circuits
38
Available Connecting Cables
Customizable
Counter Unit
port
Programming
Device
connection
switch setting
Computer
Serial
communications
mode)
Model number
Length
Peripheral port
ON
IBM PC/AT or
ibl
Peripheral bus
CS1W-CN226/626
2 m/6 m
compatible
Port: D-sub,
9-pin, male
CS1W-CN118 and
XW2Z-200S-CV/500S-CV
(Use XW2Z-
jjj
S-CV
for which ESD
countermeasures have
been taken.)
0.1 m + 2 m/5 m
Note The CS1W-CN225/-CN625/-CN227/-CN627 Connecting Cables and the
FIT10/20 CQM1-CIF11 Connecting Cables cannot be used with the Customiz-
able Counter Unit.
3-5
Fail-safe Circuits
You must set up safety circuits outside of the Customizable Counter Unit to pre-
vent dangerous conditions in the event of errors in the Unit or external power
supply. Take particular care of the following points.
WARNING
Take any safety measures necessary outside of the Unit to ensure the safety of
the system in the event of an error due to Unit malfunction or external factors.
Failure to do so could lead to a serious accident.
•
Provide interlock circuits, limit circuits, emergency stop circuits, and similar
safety measures in the PC’s external control circuits.
•
Operation will stop and all contact and pulse outputs will turn OFF when the PC
detects an error or when a FALS(07) (fatal error) instruction is executed. You
must take any safety measures necessary outside of the Unit to ensure the
safety of the system in the event that all contact and pulse outputs turn OFF.
•
It is possible for an output to remain ON or OFF due to a factors, such as dam-
age to a transistor in the internal circuit of a contact output. Provide any circuits
necessary outside of the PC to ensure the safety of the system in the event that
a contact output fails to turn OFF or ON.
•
If there is an overload or a short-circuit in the Power Supply Unit’s 24-VDC out-
put (service power supply), the voltage may drop and the outputs may turn
OFF. Take any safety measures necessary outside of the Unit to ensure the
safety of the system in the event that outputs turn OFF.
If the PC’s power supply is turned ON after the controlled system’s power supply,
contact outputs may malfunction momentarily and, as a result, the controlled
system’s outputs may operate incorrectly for a short time. To prevent any mal-
function, add an external circuit that prevents the power supply to the controlled
system from going ON before the power supply to the PC itself.
When any of the following fatal errors occur at the Customizable Counter Unit,
the Unit will stop operation (and processing) and all contact outputs and pulse
outputs will be turned OFF:
•
A Unit WDT error, a Unit RAM error, a memory error, a no END instruction error,
a FALS instruction execution, or a CYCLE TIME OVER error
Note For analog outputs, either the value set (maximum value, present value, clear)
with the output hold function in the Unit Setup Area (DM 6614) or 0 V will be out-
put. (For details, refer to 7-7 Analog Outputs.)
Set up safety circuits outside of the Customizable Counter Unit to prevent dan-
gerous conditions in the event of the above errors.
Supply Power to the PC
before Outputs
Unit Errors
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......