Section 6-2
6-2-6
Timer/Counter Area
This area is used to manage the TIM, TIMH(15), TMHH(––), CNT, and
CNTR(12) instructions. The same numbers are used for timers and counters;
do not use the same number twice even for different instructions.
If TIM/CNT number is designated for word data, it will access the present
value (PV); if it is used for bit data, it will access the Completion Flag for the
timer/counter.
The Completion Flag turns ON when the PV of the timer/counter that is being
used goes to 0.
Interrupt processing is not performed for TIMH(15), i.e., timing processing is
performed only when the instructions is executed. If the cycle time is longer
than 10 ms, counting may not be reliable.
For details on using these instructions, refer to the individual explanations in
the
Customizable Counter Units Programming Manual
(W384).
6-2-7
DM Area
This area is used in word units. The DM Area is contained in I/O memory (i.e.,
areas that can be freely read and written from the ladder program) and areas
to which functions are allocated.
Read/Write Words in
DM Area
The words in this area do not have any special functions and can be used as
required in programming. They can be read and written to using instructions
or a Programming Device.
Other Parts of DM Area
Error Log Area
When a fatal or non-fatal error occurs in the Customizable Counter Unit, the
Special I/O Unit error code and the error contents are stored automatically in
this area along with the time and date at which the error occurred.
The contents of one record are shown below:
Error contents: If the Special I/O Unit error code is 0360 Hex, the Customiz-
able Counter Unit’s error code is stored in bits 00 to 07.
Area type
Addresses
Instructions
Programming Device
Reading
Writing
Reading Writing
Read/write portion of DM Area (for
general-purpose data)
DM 0000 to
DM 6143
OK
OK
OK
OK
Area
Addresses
Instructions
Programming Device
Reading
Writing
Reading
Writing
Error Log Area
DM 6144 to
DM 6199
OK
NO
OK
OK
Special I/O Unit error code
Details 1
Details 2
Minutes
Day
Year
Seconds
Hours
Month
15
00 07
00
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......