112
AR Area
Section 6-4
AR 08
06
High-speed counter 1
status
Measuring
Flag (mea-
surement
modes 1 or
2)
OFF: Measurement for high-speed
counter rate of change or frequency
measurement is not in progress.
ON: Measurement for high-speed
counter rate of change or frequency
measurement is in progress. After
the Measurement Start Bit (bit 02 in
AR 09) is turned ON, this flag turns
ON when sampling starts (in mea-
surement mode 1) or after 2 ms has
elapsed (in measurement mode 2).
Note:
This flag is valid only when
the measurement mode set in the
Unit Setup Area (DM 6606 and
DM 6608) is set to high-speed
counter rate of change (measure-
ment mode 1) or frequency mea-
surement (measurement mode 2).
Unit
Enabled
07
High-speed
Counter
Operating
Flag
OFF: High-speed counter is
stopped.
ON: High-speed counter is operat-
ing.
08 to 15 (Reserved by system.)
Address
Bits
Function
Details
Controlled
by
Forced
set/reset