217
Troubleshooting Flowcharts
Section 9-5
I/O Check
The I/O check flowchart is based on the following ladder diagram section.
00100
00002
(LS1)
00003
(LS2)
SOL1 malfunction.
SOL1
00100
Is the IR 00100 out-
put indicator operat-
ing normally?
Yes
Monitor the ON/OFF
status of IR 00100
with a Peripheral
Device.
No
Check the voltage at the
IR 00100 terminals.
Wire correctly.
Replace the connec-
tor.
Operation OK?
Start
Is output wiring
correct?
Is terminal
block making prop-
er contact?
Disconnect external wires and
check conductivity of each
wire of terminal for 00100.
No
Yes
Check output device
SOL1.
Operation OK?
Replace the Customiz-
able Counter Unit.
Yes
No
No
Yes
No
Operation OK?
No
Yes
Yes
A
To
next
page
(See note.)
The error may be due to an output
transistor malfunction.
Summary of Contents for CS1W-HCA12-V1