222
Precautions when Using the CX-Programmer
Appendix A
5.
Select PLC – Transfer – To PLC, check Programs and Expansion Instructions, and then click the OK Button.
Specifying Operand Addresses Not Supported by the CQM1H
The program cannot be transferred from the CX-Programmer to the Customizable Counter Unit if the following
operand values are set for STIM or ACC.
STIM: C2 = 001 or C3 = 001 to 003 when C1 = 011 or 012
ACC: M = 004 to 007
Either input the instructions from the Programming Console or use dummy operands and then correct them
from the Programming Console after transferring the program to the Customizable Counter Unit.
Note
The program can be read from the Customizable Counter Unit to the CX-Programmer even if the above
operand values are set.
Setting the Unit Setup Area (DM 6600 to DM 6655)
To read or edit the Unit Setup Area, specify the DM Area addresses directly from the Memory Window. The
Memory Window can be accessed by selecting PLC – Edit – Memory from the Main Menu.
Reading the Error Log
To read the error log, specify the DM Area addresses (DM 6145 to DM 6199) directly from the Memory Win-
dow.
Checking the Ladder Program Size
The ladder program size, EM Area settings, and similar information cannot be checked from the CX-Program-
mer because the “Device Type” is set to the CQM1H. To check the ladder program size, select View – Cross-
Reference Report and then subtract the unused UM size from the total UM size to determine the amount of UM
that has been used. The program cannot be transferred to the Customizable Counter Unit if the UM Area size
is exceeded.
Monitoring the Cycle Time
The cycle time displayed when PLC – Edit – Cycle Time is selected will be 10 times the actual cycle time of the
Customizable Counter Unit. For example, if the CX-Programmer displays 10 ms, the cycle time is 1 ms.
Startup Operating Mode
If the User Setup Area is set to startup in the mode specified on the Programming Console (i.e., bits 00 to 07 of
allocated DM Area word m are set to 01 Hex) and the CX-Programmer is connected to the peripheral port on
the Customizable Counter Unit with an CS1W-CN226/626 or CS1W-CN118 + XW2Z-200/500S-CV Cable, the
Customizable Counter Unit will start in RUN mode.
Change from Programming Console Cable to CX-Programmer Cable
If the cable connecting the Programming Console is removed and the cable connecting the CX-Programmer is
connected within 2 seconds, the CX-Programmer will not go online.
PLC Information Display
The PLC information display cannot be used. (The information for the CQM1H will be displayed.)
Symbol Names
Some of the CQM1H global symbols and memory area settings registered in advance on the CX-Programmer
are not correct for the Customizable Counter Unit. These are listed in the following tables.
Summary of Contents for CS1W-HCA12-V1
Page 2: ......
Page 6: ...vi...
Page 20: ...xx Conformance to EC Directives 7...
Page 38: ...18 Models and System Configurations Section 1 2...
Page 78: ...58 Fail safe Circuits Section 3 5...
Page 138: ...118 AR Area Section 6 4...
Page 204: ...184 Improved Instructions Section 7 14...
Page 222: ...202 Cycle Time Section 8 3...
Page 240: ...220 Troubleshooting Flowcharts Section 9 5...
Page 244: ...224 Precautions when Using the CX Programmer Appendix A...
Page 252: ......
Page 253: ......