93
Error Codes
Section 11-2
Position
Control Unit
internal
errors
Unit error
MLK device
error
0026
An error has
occurred in the inter-
nal circuits of the
Position Control Unit.
Replace the Position Control Unit.
MLK device
initializa-
tion error
0030
An error has been
detected in the
MECHATROLINK
communications part
during Position Con-
trol Unit initialization
processing.
Check the MECHATROLINK communica-
tions settings in the Common Parameters,
and then restart the Unit or turn the power
OFF and ON again. If the error occurs
again, replace the Position Control Unit.
Data cor-
rupted
Memory
error
00F1
The data saved in
the Position Control
Unit is corrupted.
Transfer and save the Position Control Unit
data again, and then restart the Unit or turn
the power OFF and ON again. If the error
occurs again, replace the Position Control
Unit.
MECHA-
TROLINK
communi-
cations
errors
Scan list
mismatch
MLK initial-
ization error
0020
The MECHA-
TROLINK slave sta-
tion device
corresponding to the
axis number regis-
tered in the Position
Control Unit scan list
is not connected.
Check whether the settings for the MECHA-
TROLINK communications line connection
or slave device's station address match the
settings in the scan list, and then execute
CONNECT again.
Communi-
cations
error
MLK com-
munica-
tions error
0025
MECHATROLINK
communications
cannot be per-
formed correctly, or
two or more
MECHATROLINK
slave station devices
are using the same
station number.
Check the connection of the MECHA-
TROLINK communications cable. Remove
the noise or other the cause preventing
communications, and then restart the Posi-
tion Control Unit.
Category
Error name Error code
Probable cause
Clearing method
Summary of Contents for CX-MOTION-NCF - V1.8
Page 2: ...CXONE AL C V3 CXONE AL D V3 CX Motion NCF Ver 1 8 Operation Manual Revised October 2008...
Page 3: ...iv...
Page 5: ...vi...
Page 21: ...xxii Application Precautions 5...
Page 33: ...12 Connecting to PLC Section 2 2...
Page 36: ...15 Screen Name Section 3 1 Edit Parameter Windows...
Page 37: ...16 Screen Name Section 3 1 Monitor Windows Axis Monitor Window Unit Monitor Window...
Page 63: ...42 Editing Servo Parameters Section 5 2...
Page 68: ...47 Print Section 6 5 Print Samples An example of printed Unit Parameters is shown below...
Page 89: ...68 Writing to Flash Memory Section 7 6...
Page 103: ...82 Axis Monitor Section 8 2...
Page 109: ...88 Test Run Section 9 1...
Page 133: ...112 Index...
Page 137: ...116 Revision History...