Troubleshooting
Error
Errors that no longer guarantee the function of the safety door switch (internal errors) cause the safety outputs to be disabled immediately.
Any error that does not immediately affect the safe functionality of the safety door switch (e.g. too high ambient temperature, interference potential
at the safety outputs, cross-wire short) will lead to a warning message, disabling of the auxiliary output and a delayed shutdown of the safety
outputs. (Refer to Table 2.)
After fault rectification, the Switch can be reset by opening and relocking the relevant guard door. The safety outputs enable and allow a restart. An
interlocking chain of the safety door switch must be "locked" to enable the reactivation.
Automatic, electronic locking takes place if more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2.
To reset this type of interlocking, the safety door switch must be isolated from the power supply after elimination of the error causes.
Error warning
A fault has occurred, which causes the safety outputs to be disabled after 30 minutes. The safety outputs initially remain enabled. This signal
combination, auxiliary output disabled, and safety channels still enabled, can be used to stop the production process in a controlled manner. An
error warning is deleted when the cause of error is eliminated.
Table 1: Diagnostic information for the safety switch
The safety switch signals the switching condition as well as malfunctions via three coloured LEDs installed on the device.
*1.
After 30 min: disabling due to fault
*2.
Refer to flash code
*3.
Refer to Teaching.
Table 2: Error messages / flash codes red diagnostic LED
System condition
Solenoid control (IN)
LED
Safety outputs Y1, Y2
Auxiliary
output
OUT
Power-to-
unlock
Power-to-
lock
Green
Red
Yellow
D41G-
@
Y
D41G-
@
Z
Door open
24 V (0 V)
0 V (24 V)
On
Off
Off
0 V
0 V
0 V
Door closed,
actuator not inserted
24 V
0 V
On
Off
Off
0 V
0 V
0 V
Door closed, actuator inserted,
not locked
24 V
0 V
On
Off
Flashes
0 V
24 V
24 V
Door closed, actuator inserted,
interlocking blocked
0 V
24 V
On
Off
Flashes
0 V
24 V
0 V
Guard closed,
actuator inserted and locked
0 V
24 V
On
Off
On
24 V
24 V
24 V
Error warning (
*
1)
safety door switch locked
0 V
24 V
On
Flashes
*
2
On
24 V
*
1
24 V
*
1
0 V
Error
0 V (24 V)
24 V (0 V)
On
Flashes
*
2
Off
0 V
0 V
0 V
Additionally for variant D41G-1/-2:
Teach-in procedure actuator
started
Off
On
Flashes
0 V
0 V
0 V
Only D41G-2: Tampering
protection time
*
3
Flashes
Off
Off
0 V
0 V
0 V
Flash codes
(Red)
Designation
Autonomous
switch-off after
Error cause
1 flash pulse
Error (warning) at output Y1
30 min
Fault in output test or voltage at output Y1
2 flash pulses
Error (warning) at output Y2
30 min
Fault in output test or voltage at output Y2
3 flash pulses
Error (warning) cross-wire short
30 min
Cross-wire short between the output cables or fault at both
outputs
4 flash pulses
Error (warning) temperature too high
30 min
The temperature measurement reveals an internal temperature
that is too high
5 flash pulses
Actuator fault
0 min
Incorrect or defective actuator
6 flash pulses
Error actuator combination
0 min
An invalid combination of actuators was detected
(blocking bolt detection or tamper attempt).
Continuous red
Internal fault /
overvoltage or undervoltage fault
0 min
Device defective / supply voltage not within specifications