D41G
5
Ratings and Specifications
Model
D41G
Technical
Detection method
RFID
Frequency band
125 kHz
Transmitter outputs
-6 dBm max.
Interlock type (ISO 14119)
Type 4
Coded level (ISO 14119)
High
Actuator
*
1
D41G-A1, D41G-A2
Response time (ON to OFF)
100 ms max.
Response time (input)
1.5 ms max.
Risk time
200 ms max.
Startup time
4 s max.
Electrical
Supply voltage (Ue)
24 VDC -15%/+10% (stabilized PELV power supply)
Current consumption (Io)
0.05 A max.
Overvoltage category
III
Pollution degree
3
Operating current device with magnet switched on
Average < 0.2 A
Peak < 0.7 A/100 ms
Conditional short-circuit current
100 A
External device fuse rating
Screws or cage clamps 4 A max. (UL508 compliant)
Connector M12 2 A max.
Safety input
Switching thresholds
-3 to 5 V (low)
15 to 30 V (high)
Current consumption per input
2 mA/24 V (typical)
Accepted test pulse duration on input signal
1.0 ms max.
Test pulse interval
100 ms min.
Safety output
(OSSD)
Switching element
PNP type, short-circuit proof
Utilization category
DC-13: 24 VDC (Ue)/0.25 A (Ie)
Rated operating current (Ie)
Each 0.25 A max.
OFF-state leakage current (Ir)
0.5 mA max.
Voltage Drop (Ud)
4 V max.
Cross-wire monitoring by device
Yes
Test pulse duration
<0.5 ms
Test pulse interval
1000 ms
Auxiliary
output
Switch element
PNP type, short-circuit proof
Utilization category
DC-13: 24 VDC (Ue)/0.05 A (Ie)
Rated operating current (Ie)
0.05 A max.
Voltage drop (Ud)
4 V max.
Solenoid
Switching thresholds
-3 to 5 V (low)
15 to 30 V (high)
Power consumption
10 mA/24 V (typical)
20 mA (dynamic)
Duty ratio solenoid (ED)
100%
Accepted test pulse duration on input signal
5.0 ms max.
Test pulse interval
40 ms min.
Protection class
III
Switching frequency
1 Hz max.
Rated insulation voltage (Ui)
32 VDC
Rated impulse withstand voltage (Uimp)
0.8 kV
Minimum operating current (Im)
0.5 mA
Summary of Contents for D41G
Page 28: ...MEMO 28...