102
Using DeviceNet Scanner Demo
Section 5-2
3.
Set the Slave node address (MAC ID) and I/O size (OUT Size and IN Size).
Select
User Setup
to specify the I/O connection, and set the connection to
be used and the I/O size.
4.
Click
OK
to register the Slave in the main window.
5.
Once all the Slaves have been registered, click
Cancel
, to display the cre-
ated scan list in the main window, as shown below.
Note
The icons in the MAC ID column will be displayed in gray until the scan list is
registered to the Board.
Registering Scan Lists
Use the following procedure to register the created scan list to the Board.
1,2,3...
1.
Select
Set ScanList
from the Board menu.
2.
The icons in the MAC ID column will change from gray, as shown below,
when the scan list is registered correctly.