8
Inductive Sensors
AC/DC 2-wire Models
Note: 1. The response speed is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object,
and a set distance of half the sensing distance.
2. Power supply voltage waveform: Use a sine wave for the power supply. Using a rectangular AC power supply may result in faulty reset.
Size
M12
M18
M30
Type
Shielded
Item
E2E-X3T1
E2E-X7T1
E2E-X10T1
Sensing distance
3 mm
±
10%
7 mm
±
10%
10 mm
±
10%
Set distance
0 to 2.4 mm
0 to 5.6 mm
0 to 8.0 mm
Differential travel
10% max. of sensing distance
Sensing object
Ferrous metal (The sensing distance decreases with non-ferrous metal, refer to
Engineering Data
.)
Standard sensing object
Iron, 12 x 12 x 1 mm
Iron, 18 x 18 x 1 mm
Iron, 30 x 30 x 1 mm
Response speed
(See note 1.)
DC
1.0 kHz
0.5 kHz
0.4 kHz
AC
25 Hz
Power supply voltage
(operating voltage range) (See note 2.)
24 to 240 VDC (20 to 264 VDC)/48 to 240 VAC (40 to 264 VAC)
Leakage current
1 mA DC max., 2 mA AC max.
Control output
Load current
5 to 100 mA
Residual volt-
age
6.0 VDC max. (Load current: 100 mA, Cable length: 2 m)
10 VAC max. (Load current: 5 mA , Cable length: 2 m)
Indicator
Operation indicator (red LED), setting indicator (green LED)
Operation mode
(with sensing object approaching)
NO
For details, refer to
Timing Charts
.
Protection circuits
Output load short-circuit protection (at 20 to 40 VDC), Surge suppressor
Ambient temperature
Operating: –25
°
C to 70
°
C, Storage: –40
°
C to 85
°
C (with no icing or condensation)
Ambient humidity
Operating/Storage: 35% to 95% (with no condensation)
Temperature influence
±
10% max. of sensing distance at 23
°
C in the temperature range of –25
°
C to 70
°
C
Voltage influence
±
1% max. of sensing distance in the rated voltage range
±
15%
Insulation resistance
50 M
Ω
min. (at 500 VDC) between current-carrying parts and case
Dielectric strength
4,000 VAC at 50/60 Hz for 1 min between current-carrying parts and case
Vibration resistance
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
1,000 m/s
2
10 times each in X, Y, and Z directions
Degree of protection
IEC 60529 IP67 (JEM standard IP67g (waterproof, oil-proof))
Connection method
Pre-wired Models (standard length 2 m)
Weight (packed state)
Approx. 80 g
Approx. 140 g
Approx. 190 g
Material
Case
Brass-nickel plated
Sensing surface
PBT (polybutylene terephthalate)
Cable
PVC (polyvinyl chloride)
Clamping nuts
Brass-nickel plated
Toothed washer
Iron-zinc plated
Accessories
Instruction manual