E2K-L

 

Liquid Level Sensor

Precautions

Mounting

Mounting Procedure

• Mount the Sensor securely to the pipe using the 2 binding

bands and the 4 slip-prevention tubes provided (2 tubes
per band) in the way shown below. Mount the Sensor so
that the pipe is in contact with the entire sensing face of the
Sensor with the pipe and Sensor in parallel.

Wiring

Power Supply

• If separate power supplies are used for the Sensor and the

load, be sure to turn on the power supply to the Sensor
first.

• If a commercially available switching regulator is used, the

Sensor may malfunction because of switching noise. Con-
nect the frame ground and ground terminals to ground.

• Separate the Sensor wires from other power lines or lines

carrying high voltages. Wiring together (e.g., in the same
cable or duct) may produce inductance in the Sensor wires
resulting in malfunction or damage.

Cable Tensile Strength

• Do not use the Sensor with an excessive force exerted on

the cable. Do not exert a pulling force of more than 30 N on
the cable.

Adjustment

Sensitivity Adjustment

• Mount the Sensor with the setting position (notch) in line

with the liquid level to be detected.

• After the Sensor is mounted, adjust the detecting sensitivity

using the (12-step) sensitivity adjuster in the way shown
below.

Note 1:

While adjusting the sensitivity, do not put your hand on
the Sensor and make sure that the cable is properly
secured. Failure to observe these points may affect the
detection level.

Note 2:

When using more than one Sensor (e.g., to detect for
upper and lower limits), adjust the sensitivity of the Sen-
sors in order starting from the bottom. Adjusting the
sensitivity of a Sensor may affect the detection level of
the Sensor above it.

Correct Use

Sensor

Level of
liquid surface

Setting position
 (notch)

Pipe

Slip-prevention tubes

Binding bands

Operation
indicator

Sensitivity
adjuster

Slip-prevention tubes

Binding bands

Sensor

Pipe

Side View

Front View

Top View

Status of the 

indicator when 

the liquid level 
is aligned with 

the setting 

position

Sensitivity 

adjuster

Adjustment procedure

Not lit

Turn the sensitivity adjuster
clockwise using a screwdriver
until the indicator lights.

Lit

Turn the sensitivity adjuster
anti-clockwise using a screw-
driver until the indicator turns
OFF. Then, turn the sensitivity
adjuster clockwise until the
indicator lights again.

Pipe

Sensor

Level of
liquid surface

Setting position
 (notch)

1

1

2

2. Then set the upper limit.

1. First set the lower limit.

Summary of Contents for E2K-L

Page 1: ...4 7107 Regional Headquarters OMRON EUROPE B V Sensor Business Unit Carl Benz Str 4 D 71154 Nufringen Germany Tel 49 7032 811 0 Fax 49 7032 811 199 OMRON ELECTRONICS LLC 1 East Commerce Drive Schaumburg IL 60173 U S A Tel 1 847 843 7900 Fax 1 847 843 8568 OMRON ASIA PACIFIC PTE LTD 83 Clemenceau Avenue 11 01 UE Square 239920 Singapore Tel 65 835 3011 Fax 65 835 2711 OMRON CHINA CO LTD BEIJING OFFIC...

Page 2: ...ers allowing reductions in stock requirements Binding band Slip prevention tube 12 step sensitivity adjuster Operation indicator 20mm 24mm 33mm Little influence from bubbles Not influenced by the color of the pipe or liquid Use for pipes with diameters in the range 8 to 11 mm or 12 to 26 mm Conforms to CE standards Conforms to CE standards an indispensable requirement for semiconductor manufacturi...

Page 3: ... pipe or liquid Available in 8 to 11 mm dia and 12 to 26 mm dia models to enable sensing for a wide range of pipe diameters Space saved with built in amplifier Sensing method Applicable pipe diameters Appearance Output format Model number Electrostatic capacity method 8 to 11 mm dia NPN open collector output NO E2K L13MC1 12 to 26 mm dia E2K L26MC1 Liquid surface level detection ...

Page 4: ...on of liquid surface Notch position For details refer to Sensitivity Adjustment on page 6 Indicator Operation indicator orange Ambient temperature Operating 0 to 55 C Storage 10 to 65 C with no icing or condensation Ambient humidity Operating storage 25 to 85 with no condensation Temperature influence In the range 0 to 55 C Detection level at 23 C 4 mm with distilled water or 20 concentration salt...

Page 5: ...ence of Surrounding Objects Units mm Mutual Interference When installing 2 or more Sensors in series in parallel or facing each other be sure that they are separated by at least the distances shown below Mutual Interference Units mm The detection level for the top Sensor may change when the detection level for the bottom Sensor is set Be sure to set the detection level for the bottom Sensor first ...

Page 6: ...el to be detected After the Sensor is mounted adjust the detecting sensitivity using the 12 step sensitivity adjuster in the way shown below Note 1 While adjusting the sensitivity do not put your hand on the Sensor and make sure that the cable is properly secured Failure to observe these points may affect the detection level Note 2 When using more than one Sensor e g to detect for upper and lower ...

Page 7: ...s in temperature because this will shorten the service life Miscellaneous Drift may occur when the power supply is turned ON If the dielectric constant of the liquid is low the detection level of the liquid may be 2 to 3 mm higher than the set level for approximately 20 minutes after power is turned ON Dimensions Units mm Correct Use 20 5 43 41 33 R6 5 24 11 5 1 5 6 5 1 3 5 6 6 Sensitivity adjuste...

Reviews: