A Appendices
A - 28
E3NW-ECT EtherCAT Digital Sensor Communication Unit Operation Manual (E429)
•
This object sets the threshold 1 setting for the Sensor Amplifier with the unit number that is specified
by the index.
•
Threshold 1 is used in Normal Detection Mode or as the low threshold in Area Detection Mode.
•
The setting range of the FA0, LA0, or SA0 is
−
1,999 to 9,999 (FFFF F831 to 0000 270F hex).
•
The setting range for the TA0 is
−
19,999,999 to 99,999,999 (FECED301 to 05F5E0FF hex).*
•
The setting range of the AA0 or VA0 is
−
1999.9999 to 9999.9999.
* Items with asterisks are supported from E3NW-ECT version 1.03.
You can check the version with object index 100A hex. (Refer to "A-1-4 Communication Objects" on page A-4.)
•
This object sets the threshold 2 setting for the Sensor Amplifier with the unit number that is specified
by the index.
•
Threshold 2 is used as the high threshold in Area Detection Mode.
•
The setting range of the FA0, LA0, SA0, FAH0, or MA0
*2
is
−
1,999 to 9,999 (FFFF F831 to 0000 270F
hex).
•
The setting range for the TA0 is
−
19,999,999 to 99,999,999 (FECED301 to 05F5E0FF hex).
*1
•
The setting range of the AA0 or VA0 is
−
1999.9999 to 9999.9999 (FECED301 to 05F5E0FF hex).
*1 Items with asterisks are supported from E3NW-ECT version 1.03.
*2 Items with asterisks are supported from E3NW-ECT version 1.08.
You can check the version with object index 100A hex. (Refer to "A-1-4 Communication Objects" on page A-4.)
4004 + (N-1)
×
80
hex
No_01 ... 30 Threshold 1 Settings
Subindex 0: Number of Entries
Range: 02 hex
Unit: ---
Default: 02 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Threshold 1 Settings IN1
Range:
−
2,147,483,648 to
2,147,483,647
(8000 0000 to 7FFF FFFF hex)
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (INT32)
Access: RW
PDO map: Possible
Subindex 2: No_01 ... 30 Threshold 1 Settings IN2
Range:
−
2,147,483,648 to
2,147,483,647
(8000 0000 to 7FFF FFFF hex)
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (INT32)
Access: RW
PDO map: Possible
4005 + (N-1)
×
80
hex
No_01 ... 30 Threshold 2 Settings
Subindex 0: Number of Entries
Range: 02 hex
Unit: ---
Default: 02 hex
Attribute: ---
Size: 1 byte (U8)
Access: RO
PDO map: Not possible
Subindex 1: No_01 ... 30 Threshold 2 Settings IN1
Range:
−
2,147,483,648 to
2,147,483,647
(8000 0000 to 7FFF FFFF hex)
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (INT32)
Access: RW
PDO map: Possible
Subindex 2: No_01 ... 30 Threshold 2 Settings IN2
*2
Range:
−
2,147,483,648 to
2,147,483,647
(8000 0000 to 7FFF FFFF hex)
Unit: ---
Default: --- hex
Attribute: A
Size: 4 bytes (INT32)
Access: RW
PDO map: Not possible
Summary of Contents for E3NW-ECT
Page 1: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429 E1 07...
Page 3: ...E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual Revised December 2017...
Page 4: ......
Page 170: ...Revision 2 E3NW ECT EtherCAT Digital Sensor Communication Unit Operation Manual E429...
Page 171: ......