Section 3
Explicit Message Communications
■
Read Command List
A list of Explicit Message Read commands is shown below.
[Supported Models]
E3X-DA7-S, E3X-DA9-S: DA7, E3X-DA-S: DA, E3X-MDA: MDA, E3X-DATW-S: TW,
E3X-DARM-S: RM; E3X
E3C-LDA (2 output types): LDATW, E3C-LDA (input type): LDARM; E3C
E2C-EDA (2 output types): EDATW, E2C-EDA (input type): EDARM; E2C
Explicit Messages
Functions
Command
Supported
Model
Class
ID
Instance
ID
Attribute
ID
Read status
Reads the status of the sensor
communication unit.
9F
0
AA
—
Read detection level With specifying a Unit No. with the Instance
ID, reads the digital detection level.
9F
Unit
Number
82
All models
Read detection level
+ ON/OFF output
data
With specifying a Unit No. with the
Instance ID, reads the detection level and
ON/OFF output.
9F
Unit
Number
81
All models
When detected (ON)
Read detection level
With specifying a Unit No. with the
Instance ID, reads the detection level
when detected (ON).
9F
Unit
Number
96
All models
When detected (ON)
Read detection level
With specifying a Unit No. with the
Instance ID, reads the detection level
when not detected (OFF).
9F
Unit
Number
97
All models
Read Threshold
Settings
With specifying a Unit No. with the
Instance ID, reads the threshold value.
9C
Unit
Number
11
All models
Read Differentiation
Threshold Settings
With specifying a Unit No. with the Instance
ID, reads the differentiation mode
threshold.
9C
Unit
Number
10
Except DA,
and MDA
Read Difference
Threshold Settings
With specifying a Unit No. with the
Instance ID, reads the threshold value
when the difference outputs.
9C
Unit
Number
12
MDA
Read Operating
Mode Settings
With specifying a Unit No. with the
Instance ID, reads the operating mode.
9C
Unit
Number
20
DA7, TW, MDA,
LDATW, EDATW
Read Detection
Function Settings
With specifying a Unit No. with the
Instance ID, reads the detection mode.
9C
Unit
Number
21
All models
Read Differentiation
Edge Settings
With specifying a Unit No. with the
Instance ID, reads the differentiation
edge.
9C
Unit
Number
22
Except DA,
and MDA
Differentiation mode
Read Response
Time
With specifying a Unit No. with the
Instance ID, reads the differentiation
mode response time.
9C
Unit
Number
23
Except DA,
and MDA
Read Timer
Function Settings
With specifying a Unit No. with the
Instance ID, reads the timer function.
9C
Unit
Number
24
All models
Read Timer Time
Settings
With specifying a Unit No. with the
Instance ID, reads the timer time.
9C
Unit
Number
25
All models