CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
E5CK
6--8
Parameter No.
Parameter
Data Setting Range
Mode
57
Input type
0 to 21
59
Scaling upper limit
Scaling lower limit +1 to 9999
58
Scaling lower limit
--1999 to scaling upper limit --1
60
Decimal point
0 to 3
30
_
C/
_
F selection
0 :
_
C, 1 :
_
F
61
Control output 1 assignment
0 to 4, 6
62
Control output 2 assignment
0 to 4, 6
63
Auxiliary output 1 assignment
2 to 4, 6 to 8
Setup
65
Alarm 1 type
1 to 11
Setup
66
Alarm 1 open in alarm
0: closed in alarm, 1: open in alarm
67
Alarm 2 type
1 to 11
68
Alarm 2 open in alarm
0: closed in alarm, 1: open in alarm
69
Alarm 3 type
1 to 11
70
Alarm 3 open in alarm
0: closed in alarm, 1: open in alarm
71
Direct/Reverse operation
0: Reverse operation, 1: Direct operation
28
Set point upper limit
*5
Set point lower limit +1 to scaling upper limit
27
Set point lower limit
*5
Scaling lower limit to Set point upper limit --1
72
PID / ON/OFF
0: Advanced PID, 1: ON/OFF
73
ST
0 : OFF, 1 : ON
34
ST stable range width
0.1 to 999.9
35
α
0.00 to 1.00
Expansion
85
AT calculated gain
0.1 to 10.0
Expansion
37
Standby sequence reset method
0, 1
36
Automatic return of display mode
0 to 99
93
AT hysteresis
0.1 to 9.9
55
LBA detection width
0.0 to 999.9
*1 See page 5-22.
*2 0: Control output (heat), 1: Control output (cool), 2: Alarm 1, 3: Alarm 2, 4: Alarm 3, 6: LBA.
*3 2: Alarm 1, 3: Alarm 2, 4: Alarm 3, 6: LBA, 7: Error 1, 8: Error 2
*4 See page 5-25.
*5 During temperature input, the range becomes the range of use of the selected sensor.
*6 See page 5-30.
To read the E5CK controller status, use the X format “RX” command. For details,
see the Appendix: X Format Head List (page A-13).
Reading the status