CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
E5CK
6--10
6.5 How to Read Communications Error Information
The result of communications on the E5CK can be checked by the end code in the response frame. Use this
end code to remedy errors that may occur.
Communications are normal when the end code in the response is “00”.
If the end code is not “00”, this indicates that an error other that is not an
undefined error has occurred. The end code format is as follows and does
not contain a data area.
CR
Unit
No.
Command
code
FCS
Command type
End
code
@
*
2B
2B
1B
2B
2B
2B
End code
0D
Code name
Command cannot be executed
•
Writing was carried out during local operation.
•
Writing was carried out during executing auto-tuning.
•
An attempt was made to execute 40%AT during heating and cooling con-
trol.
•
An attempt was made to switch run/stop in setting level 1.
•
An attempt was made to execute AT in setting level 1.
•
Issue the parameter read or write commands in conditions other than above.
End code
10
Code name
Parity error
Parity check error was detected in the received data.
Check the communications condition. If the communications condition of
the host computer and E5CK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5CK controller.
End code
11
Code name
Framing error
Stop bit cannot be detected.
Check the communications condition. If the communications condition of
the host computer and E5CK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5CK controller.
Responses are not returned unless the target unit for communications and the unit
No. in the command match.
About the unit No.
J
End code
F
Description
F
Action
F
Description
F
Action
F
Description
F
Action