6.5 How to Read Communications Error Information
E5CK
6--11
End code
12
Code name
Overrun error
The receive buffer overflowed.
Check the communications condition. If the communications condition of
the host computer and E5CK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5CK controller.
End code
13
Code name
FCS error
The FCS (Frame Check Sequence) do not match.
Check the FCS program.
End code
14
Code name
Format error
The received command length does not match the length defined in the
frame format.
Check the communications condition. If the communications condition of
the host computer and E5CK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5CK controller.
End code
15
Code name
Setting range error
Numerical values or code values in the data are not within the setting
range.
Check the parameter and read or write data of special commands.
J
Undefined error
CR
Unit
No.
FCS
@
*
2B
2B
2B
2B
C
I
•
An undefined header code has been received.
•
A currently invalid parameter (e.g. the scaling command during temper-
ature input) has been received.
•
Check the parameter No.
F
Description
F
Action
F
Description
F
Action
F
Description
F
Action
F
Description
F
Action
F
Description
F
Action