CHAPTER 1 INTRODUCTION
E5CK
1--4
1.2 Input and Output
Alarm 2
Temperature
input
Voltage input
Current input
Event input
Controller
Control output
(heat)
Control output
(cool)
Alarm 1
Alarm 3
LBA
Error 1
Error 2
Control output
1
Control output
2
Auxiliary
output 1
Transfer
output 1
Input type
jumper
The E5CK supports four inputs.
F
Temperature input/Voltage input/Current input
•
Only one of temperature input, voltage input and current input can be
selected and connected to the controller. The above figure shows temper-
ature input connected to the controller.
•
The following input sensors can be connected for temperature input:
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
•
The following currents can be connected for current input:
4 to 20 mA, 0 to 20 mA
•
The following voltages can be connected for voltage input:
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
When using event input, add on the input unit (E53---CKB).
You can select from the following five event inputs:
Multi-SP
Run/Stop
Auto/Manual
J
Input
F
Event input