SPECIFICATIONS
E5CK
A--3
J
Characteristics
Indication Accuracy
Thermocouple:
(
±
0.3%
of indication value or ±
1
°
C, whichever greater)
±
1 digit max. (*1)
Platinum resistance thermometer:
(
±
0.2% of indication value or
±
0.8
°
C whichever greater)
±
1 digit max.
Analog input:
±
0.2%
±
1 digit max.
Temperature variation influ-
ence (*2)
Platinum resistance thermometer:
(
±
1% of PV or
±
2
°
C, whichever greater)
±
1 digit max.
Thermocouple (R, S, B, W):
(
±
1% of PV or
± 10
°
C whichever greater)
±
1 digit max
Voltage variation influence
(*2)
(
±
1% of PV or
± 10
°
C, whichever greater)
±
1 digit max.
Other thermocouples (K1, K2, J1, J2, E, N, T, L1, L2, U, PLII):
(
±
1% of PV or
± 4
°
C, whichever greater)
±
1 digit max.
Analog input (current, voltage, or remote SP input):
±
1%FS
±
1 digit max.
Hysteresis
0.01 to 99.99%FS (in units of 0.01%FS)
Proportional Band (P)
0.1 to 999.9% FS (in units of 0.1%FS)
Integral (reset) Time (I)
0 to 3999 s (in units of 1 second)
Derivative (rate) Time (D)
0 to 3999 s (in units of 1 second)
Control Period
1 to 99 s (in units of 1 second)
Manual Reset Value
0.0 to 100.0% (in units of 0.1%)
Alarm Setting Range
-1999 to 9999 or -199.9 to 999.9 (decimal point position dependent on input
type)
Sampling Period
Temperature input: 250 ms, Analog input: 100 ms
Insulation Resistance
20 M
Ω
min. (at 500 VDC)
Dielectric Strength
2000 VAC, 50/60Hz for 1 min (between terminals of different polarities)
Vibration
Malfunction 10 to 55 Hz, 10 m/s
2
(1G) for 10 min each in X, Y, and Z directions
Vibration
Resistance
Destruction 10 to 55 Hz, 20 m/s
2
(2G) for 2hrs each in X, Y, and Z directions
Shock Resis-
tance
Malfunction 200 m/s
2
min. (20G), 3 times each in 6 directions (100 m/s
2
(10G) applied to the
relay)
tance
Destruction 300 m/s
2
min. (30G), 3 times each in 6 directions
Weight
Approx. 170 g, adapter: approx. 10 g
Enclosure Ratings
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory Protection
Non-volatile memory (Write operation : 100000 max.) (*3)
*1The indication accuracy of the K1, T, and N thermocouples at a temperature of -100
°
C or less is ±2
°
C ±1 digit maximum. The
indication accuracy of the U, L1 and L2 thermocouples at any temperature is ±2
°
C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400
°
C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200
°
C or less is ±3
°
C ±1 digit maximum.
The indication accuracy of the W thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±3
°
C of the indicated
value.
The indication accuracy of the PLII thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±2
°
C of the indicated
value.
*2 Ambient temperature: ---10
°
C to 23
°
C to 55
°
C
Voltage range: ---15 to +10% of rated voltage
*3 Write operations: Parameter changes, remote/local selection, etc.