APPENDIX
E5CK
A--4
J
Output Unit Ratings and Characteristics
Relay output
SPST, 250 VAC, 3A (resistive load)
Mechanical life expectancy: 10,000,000 operations min
Electrical life expectancy: 100,000 operations min
Voltage Output (NPN)
NPN, 12 VDC, 20 mA (with short-circuit protection)
Voltage Output (PNP)
PNP, 12 VDC, 20 mA (with short-circuit protection)
Linear Voltage Output
0 to 10 VDC, Permissible load impedance: 1 k
Ω
min., Resolution:
Approx. 2600
Linear Current Output
4 to 20 mA, Permissible load impedance: 500
Ω
max., Resolution:
Approx. 2600
Linear Current Output
0 to 20 mA, Permissible load impedance: 500
Ω
max., Resolution:
Approx. 2600
J
Option Unit Ratings and Characteristics
Contact input
ON: 1 k
Ω
max., OFF: 100 k
Ω
min.
Event inputs
No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA
max.
Communications
Interface
:RS-232C or RS-485
Transmission method
:Half-duplex
Synchronization method
:Start-stop synchronization (asynchronous method)
Baud rate
:1.2/2.4/4.8/9.6/19.2 kbps
Transfer output
4 to 20 mA, Permissible load impedance: 500
Ω