1.2 Input and Output
E5CK
1--5
J
Output
The E5CK supports the following four outputs.
Control output 1
Control output 2
Auxiliary output 1
Transfer output
When using control outputs 1 and 2, set the output unit (sold separately).
Eight output units are available to suit the output circuit configuration.
When using transfer output, add on the communication unit (E53---CKF).
Note:
The output functions of the E5CK do not operate for five seconds af-
ter the E5CK is turned ON.
The E5CK supports the following eight output functions.
Control output (heat)
Control output (cool)
Alarms 1 to 3
LBA
Error 1 (input error)
Error 2 (A/D converter error)
Assign these output functions to control outputs 1 and 2 and auxiliary out-
put 1.
Only control output (heat), control output (cool), alarms 1 to 3, and LBA
can be assigned to control outputs 1 and 2. Also, only alarms 1 to 3, LBA,
and errors 1 and 2 can be assigned to auxiliary output 1.
In the example on the previous page, “control output (heat)” is assigned
to “control output 1”, “alarm 1” is assigned to “control output 2”, and
“alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configura-
tion is such that heating control output is connected to control output 1,
and alarm output is connected to control output 2 and auxiliary output 1.
In a heating and cooling control, assign “control output (cool)” to either
of “control output 1” or “control output 2”.
The E5CK supports the following five transfer outputs.
Set point
Set point during SP ramp
Process value
Heating side manipulated variable
Cooling side manipulated variable
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse
scaling can also be carried out.
F
Output assign-
ments
F
Transfer output