APPENDIX
E5CK
A--6
SETTING LIST
Mode
Parameter Name
Setting Range
Unit
Default
Remarks
Setting
Protect
Security
0 to 6
None
1
Protect
[A/M] key protect
ON/OFF
None
OFF
Manual
Manual MV
-5.0 to 105.0
%
0.0
Level 0
Set point
Set point lower limit to Set point upper limit
EU
0
Level 0
Run/Stop
Run/Stop
None
RUN
AT Execute/Cancel
OFF/AT-1/AT-2
None
OFF
During running
Set point 0
Set point lower limit to Set point upper limit
EU
0
Multi-SP
Set point 1
Set point lower limit to Set point upper limit
EU
0
Multi-SP
Alarm value 1
-1999 to 9999
EU
0
Alarm value 2
-1999 to 9999
EU
0
Alarm value 3
-1999 to 9999
EU
0
Proportional band
0.1 to 999.9
%FS
10.0
Integral time
0 to 3999
sec
233
Level 1
Derivative time
0 to 3999
sec
40
Cooling coefficient
0.01 to 99.99
None
1.00
At heating and
cooling control
Dead band
-19.99 to 99.99
%FS
0.00
At heating and
cooling control
Manual reset value
0.0 to 100.0
%
50.0
Hysteresis (heat)
0.01 to 99.99
%FS
0.10
Hysteresis (cool)
0.01 to 99.99
%FS
0.10
At heating and
cooling control
Control period (heat)
1 to 99
sec
20
Control period (cool)
1 to 99
sec
20
At heating and
cooling control
Remote/Local
RMT/LCL
None
LCL
SP ramp time unit
M(Minutes) / H(Hours)
None
M
SP ramp set value
0 to 9999
EU
0
LBA detection time
0 to 9999
Sec
0
MV at stop
-5.0 to 105.0
%
0.0
MV at PV error
-5.0 to 105.0
%
0.0
MV upper limit
MV lower limit + 0.1 to 105.0
%
105.0
Level 2
MV lower limit
-5.0 to MV upper limit -0.1
%
-5.0
MV change rate limit
0.0 to 100.0
%/sec
0.0
Input digital filter
0 to 9999
sec
0
Alarm 1 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 2 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 3 hysteresis
0.01 to 99.99
%FS
0.02
Input shift upper limit
-199.9 to 999.9
°
C/
°
F
0.0
Temperature input
Input shift lower limit
-199.9 to 999.9
°
C/
°
F
0.0
Temperature input
*1 During heat and cooling control, the lower limit becomes -105.0%.
*2 During heat and cooling control, the setting range becomes 0.0 to 105.0%.
*3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.
*1
*1
*1
*2
*3