SETTING LIST
E5CK
A--7
Mode
Parameter Name
Setting Range
Unit
Default
Remarks
Setting
Input type
0 to 21
None
2
Scaling upper limit
Scaling lower limit +1 to 9999
EU
-100
Analog input
Scaling lower limit
-1999 to SP setting upper limit -0.1
EU
0
Analog input
Decimal point
0 to 3
None
0
Analog input
_
C/
_
F selection
_
C/
_
F
None
_
C
Temperature input
Parameter initialize
Yes/No
None
NO
Control output 1 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm
3/LBA
None
HEAT
Control output 2 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm
3/LBA
None
AL-1
Setup
Auxiliary output 1 assignment
Alarm 1/Alarm 2/Alarm 3/LBA/
S.ERR/E333
None
AL-2
Setup
Alarm 1 type
1 to 11
None
2
Output assignment
needed
Alarm 1 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 2 type
1 to 11
None
2
Output assignment
needed
Alarm 2 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Alarm 3 type
1 to 11
None
2
Output assignment
needed
Alarm 3 open in alarm
N-O/N-C
None
N-O
Output assignment
needed
Direct/Reverse operation
OR-D/OR-R
None
OR-R
Set point upper limit
Set point lower limit +1 to scaling
upper limit
None
1300
Set point lower limit
Scaling lower limit to Set point upper
limit -1
None
-200
PID/ON/OFF
PID / ON/OFF
None
PID
ST
OFF/ON
None
OFF
E
ST stable range
0.1 to 999.9
°
C/
°
F
15.0
ST=ON
Expan-
sion
α
0.00 to 1.00
None
0.65
sion
AT calculated gain
0.1 to 10.0
None
1.0
Standby sequence reset set-
ting method
0/1
None
0
Automatic return of display
mode
0 to 99
Sec
0
AT hysteresis
0.1 to 9.9
%FS
0.2
LBA detection width
0.0 to 999.9
%FS
0.2
Multi-SP function
0/1
None
0
Event input assignment 1
STOP/MAN
None
STOP
Communication stop bit
1/2
bits
2
Communication data length
7/8
bits
7
Option
Communication parity
None/Even/Odd
None
EVEN
Option
Communication baud rate
1.2/2.4/4.8/9.6/19.2
kbps
9.6
Communication unit No.
0 to 99
None
0
Transfer output type
SP/SP-M/PV/O/C-O
None
SP
Transfer output upper limit
*5
*5
*5
Transfer output lower limit
*5
*5
*5
*4 When temperature input is selected, the sensor range selected in the “input type” parameter (setup mode) corresponds
to the scaling upper and lower limit value.
*5 Set the transfer output type parameter according to the following table.
Transfer Output Type
Transfer Output Lower Limit to Transfer Output Upper Limit
SP
:Set point
Set point lower limit to Set point upper limit
SP-M
:Set point during SP ramp
Set point lower limit to Set point upper limit
PV
:Process value
Scaling lower limit to scaling upper limit
O
:Manipulated variable (heat)
-5.0 to 105.0%
C-O
:Manipulated variable (cool)
0.0 to 105.0%
D
The output ranges of the SP setting, set point or process value when temperature input is selected are the ranges supported
by the selected sensor.
D
When the heating side manipulated variable or cooling side manipulated variable is selected, the transfer output lower limit in
a heating and cooling control becomes “0.0”.
*4
*4
*4
*2
*2
*4