2.3 Wiring Terminals
E5CK
2--7
•
Connect the input to terminal Nos. 6 to 8 as follows according to the
input type.
8
7
6
8
7
6
8
7
6
8
7
6
-
+
-
+
-
+
V
mA
TC
⋅
PT
V
I
Thermocouple Platinum resistance
thermometer
Voltage input
Current input
•
Match the inputs with the internal jumper settings for each input type.
For thermocouple or platinum resistance thermometer inputs, set the
inputs to a common position (TC/PT) as the temperature input. For
details on jumper connector positions, see page 2-2.
•
Terminal Nos. 11 and 12 are for control output 1 (OUT1). The five out-
put types and internal equalizing circuits are available according to out-
put unit:
11
12
11
12
L
11
12
L
11
12
L
11
12
L
E53-R4R4
E53-Q4R4
E53-Q4Q4
E53-Q4HR4
E53-Q4HQ4H
E53-V44R4
E53-C4R4
E53-C4DR4
NPN
PNP
0 to 10V
4 to 20mA/0 to 20mA
+v
+
-
+
-
+
-
+
-
GND
mA
Relay
V
GND
+v
•
Terminal Nos. 9 and 10 are for control output 2 (OUT2). The three out-
put types and internal equalizing circuits are available according to out-
put unit:
10
9
10
9
L
10
9
L
+v
+
-
+
-
GND
E53-Q4Q4
E53-Q4HQ4H
NPN
PNP
E53-R4R4 /E53-V44R4
E53-Q4R4 /E53-C4R4
E53-Q4HR4/E53-C4DR4
Relay
GND
+v
•
The following table shows the specifications for each output type.
Output Type
Specifications
Relay
Voltage (NPN)
Voltage (PNP)
250VAC, 3 A
12VDC, 20 mA (with short-circuit protection)
12VDC, 20 mA (with short-circuit protection)
0 to 10V
4 to 20mA
0 to 20mA
0 to 10VDC, Permissible load impedance:
1 k
Ω
min., Resolution: Approx. 2600
4 to 20 mA, Permissible load impedance:
500
Ω
max., Resolution: Approx. 2600
0 to 20 mA, Permissible load impedance:
500
Ω
max., Resolution: Approx. 2600
F
Input
5
4
3
2
1
10
9
8
7
6
13 14
11 12
F
Control output
5
4
3
2
1
10
9
8
7
6
13 14
11 12