3.6 Starting and Stopping Operation
E5CK
3--11
3.6 Starting and Stopping Operation
•
You can start and stop operation by changing the setting of the “run/
stop” parameter (level 0 mode).
•
You can switch the RUN/STOP function up to 100,000 times.
•
To stop operation, set the “run/stop” parameter to [
] (stop). In a
stop state, the “STOP” LED lights.
•
To set output during a stop, specify the manipulated variable (Standard:
-5.0 to 105.0%, Heating and cooling: -105.0 to 105.0%) in the “MV at
stop” parameter (level 2 mode). Factory setting is “0.0: 0.0%”.
The following example describes the procedure to follow to stop control
during operation of the controller.
(1) Select the menu display, and select [
] (level 0 mode) using the
or
keys. For details on selecting the menu display, see page
1-7.
(2) Press the
key to enter the level 0 mode. The PV and SP are dis-
played.
(3) Press the
key until [
] (“run/stop” parameter) is displayed.
(4) Press the
key to select [
] (stop). The “STOP” LED lights,
and operation stops.
To resume operation, follow the above procedure to select [
] (“run”).
The “STOP” LED goes out and operation starts.
F
Manipulated vari-
able at stop
Setting Example