In this mode, manual operations are possible, and the “MANU” LED lights.
•
When this mode is selected, the manipulated variable that was active immediately
before the mode was switched to is output. When changing the manipulated variable,
change it using the
or
keys. When this mode is selected during auto-tuning,
auto-tuning is canceled.
•
To select this mode when in the level 0 to 2 modes, press the
A/M
key for 1 second mini-
mum. To exit this mode, press the
A/M
key for 1 second minimum. The mode changes
to the level 0 mode.
•
“Manual MV” is the only parameter available in this mode.
Manual MV
•
Set the manipulated variable for manual operation.
•
The process value is displayed on the No.1 display, and the manipulated variable is
displayed on the No.2 display. Change the manipulated variable using the
or
keys.
Process value
Manipulated variable
[MANU] LED
The manual manipulated variable is held when the power is interrupted.
Control Method
Setting Range
Unit
Default
Standard
-5.0 to 105.0
%
0
Heating and cooling
-105.0 to 105.0
%
0
F
Related article
3.7 Adjusting Control Operation (page 3-12)
Manual Mode
Function
Comment