CHAPTER 5 PARAMETERS
E5CK
5--10
AT Execute/Cancel
Conditions of Use
The controller must be in operation, con-
trol must be advanced PID control, and ST
must be set to OFF.
•
Selects the limit cycle of MV change width (40% or 100%) for execution. After AT
execution, the “PID” and the “LBA detection time” (LBA: Loop Break Alarm) param-
eters are set automatically.
•
During heating and cooling control, only 100%AT can be executed.
•
When this parameter is selected, the setting becomes [
].
•
To execute 40%AT, select [
], and to execute 100%AT, select [
]. During
execution of auto-tuning, the AT LED flashes. However, note that during heating and
cooling control, [
] is not displayed.
•
When AT execution ends, the parameter setting automatically returns to [
].
F
Related article
3.7 Adjusting Control Operation (page 3-13)
F
Related parameters
“Run/Stop” (level 0 mode)
“Proportional band” “Integral time” “Derivative time” (level 1 mode)
“LBA detection time” (level 2 mode)
Set point 0
Set point 1
Conditions of Use
The multi-SP function must be in
operation.
•
When event input is OFF, the “set point 0” parameter is used, and when ON, the “set
point 1” parameter is used.
•
When the “set point” parameter has been changed, the setting of whichever is
selected in event input, “set point 0” or “set point 1”, is linked and changed.
•
The decimal point position is dependent on the selected sensor during temperature
input and on the results of scaling during analog input.
Setting Range
Unit
Default
Scaling lower limit to Scaling upper limit
EU
0
F
Related article
4.3 How to Use Option Functions (page 4-8)
F
Related parameters
“Multi-SP function” (option mode)
“Set point” (level 0 mode)
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
Level 1 Mode