CHAPTER 5 PARAMETERS
E5CK
5--12
Cooling coefficient
Conditions of Use
The control must be heating and cooling
control, and advanced PID control.
•
In heating and cooling control, P at the cooling side is calculated by the following for-
mula:
Cooling side P = cooling coefficient
¢
P
Setting Range
Unit
Default
0.01 to 99.99
None
1.00
F
Related article
4.1 Selecting the Control Method (page 4-2)
F
Related parameter
“Proportional band” (level 1 mode)
Dead band
Conditions of Use
The control system must be heating and
cooling control.
•
Sets the output dead band width in a heating and cooling control system. A negative
setting sets an overlap band.
Setting Range
Unit
Default
-19.99 to 99.99
%FS
0.00
F
Related article
4.1 Selecting the Control Method (page 4-2)
Level 1 Mode
Function
Comment
See
Function
Comment
See