E5CK
5--13
Manual reset value
Conditions of Use
The control must be standard control,
advanced PID control, ST must be set to
OFF, and the “integral time” parameter
must be set to “0”.
•
Sets the required manipulated variable to remove offset during stabilization of P or
PD control.
Setting Range
Unit
Default
0.0 to 100.0
%
50.0
Hysteresis (heat)
Hysteresis (cool)
Conditions of Use
The control system must be ON/OFF con-
trol.
•
Sets the hysteresis for ensuring stable operation at ON/OFF switching.
•
In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)”
parameter cannot be used.
•
In heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the “hysteresis (heat)” parameter to set the heating side hysteresis,
and use the “hysteresis (cool)” parameter to set the cooling side hysteresis.
Parameter
Setting Range
Unit
Default
Hysteresis (heat)
0.01 to 99.99
%FS
0.10
Hysteresis (cool)
0.01 to 99.99
%FS
0.10
F
Related article
4.1 Selecting the Control Method (page 4-3)
F
Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
“PID / ON/OFF” (expansion mode)
Level 1 Mode
Function
Comment
Function
Comment
See