CHAPTER 5 PARAMETERS
E5CK
5--14
Control period (heat)
Control period (cool)
Conditions of Use
Relay or voltage output must be set as the
outputs, and the control must be set to
advanced PID control.
•
Sets the pulse output period. Set the control period taking the control characteristics
and life expectancy of the controller into consideration.
•
In standard control, use the “control period (heat)” parameter. The “control period
(cool)” parameter cannot be used.
•
In heating and cooling control, the control period can be set independently for heat-
ing and cooling. Use the “control period (heat)” parameter to set the heating side con-
trol period, and use the “contrlo period (cool)” parameter to set the cooling side con-
trol period.
Parameter
Setting Range
Unit
Default
Control period (heat)
1 to 99
Second
20
Control period (cool)
1 to 99
Second
20
F
Related article
3.3 Setting Output Specifications (page 3-5)
F
Related parameters
“Control output 1 assignment” “Control output 2 assignment” (setup mode)
Level 1 Mode
Function
Comment