CHAPTER 5 PARAMETERS
E5CK
5--16
Remote/Local
Conditions of Use
The communications function must be in
use.
•
Switches between remote and local operation.
•
To change the parameter setting during remote operation, use the communications
function. To change the parameter setting during local operation, change the setting
on the E5CK controller.
•
You can check the parameter setting by both communications and on the E5CK con-
troller regardless of whether the controller is switched to remote or local operation.
Setting Range
Default
[
]: remote / [
]: local
[
]
SP ramp time unit
SP ramp set value
Conditions of Use
ST must be set to OFF.
•
Specifies the change rate during SP ramp operation. Set the maximum permissible
change width per unit of time (minute or hour) as the “SP ramp set value”. However,
note that when set to “0”, the SP ramp function is disabled.
•
The time unit and SP ramp set value are independent of each other. For example,
when setting “30 per minute”, set the “SP ramp set value” parameter to “30” and the
“SP ramp time unit” parameter to [
] (“minute”). However, if you change the
time unit only to [
] (“hour”), the set time becomes “30 per hour.”
•
During temperature input, the decimal point position of the SP ramp set value is
dependent on the currently selected sensor, and during analog input on the results
of scaling.
Parameter
Setting Range
Unit
Default
SP ramp time unit
[
]: minute/
[
]: hour
None
SP ramp set value
0 to 9999
EU
0
During temperature input, the range of the currently selected sensor it taken as the
setting range for the “SP ramp set value” parameter.
F
Related article
4.2 Operating Condition Restrictions (page 4-5)
F
Related parameters
“Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup
mode)
Level 2 Mode
Function
Comment
Function
Comment
See